The Megger TORKEL 900 is a high-performance battery discharge test system designed for accurate capacity testing and condition assessment of stationary battery banks used in substations, power plants, telecommunications, UPS systems, and industrial facilities. It enables controlled discharge testing to verify battery performance, identify weak cells, and ensure the reliability of critical DC power systems. Its modular design and high discharge capability make it suitable for testing a wide range of battery technologies, including lead-acid and nickel-cadmium batteries.
Technical Highlights: Discharge current: up to 220 A (standalone) and expandable to higher currents with additional load units | Voltage range: 12–300 V DC | Supports constant current, constant power, constant resistance, and profile discharge modes | Real-time monitoring of battery voltage, discharge current, capacity, and elapsed time | Automatic test termination based on voltage, capacity, time, or ampere-hour limits | Integrated data logging and reporting | Compatible with battery voltage monitoring systems for individual cell analysis | Rugged portable design for field and substation applications.
Ideal for battery capacity testing, preventive maintenance programs, battery health assessment, commissioning of new battery banks, and reliability verification of critical DC backup power systems.