top of page
Omicron CP TD1 - Capacitance & Tan Delta Test Unit

Omicron CP TD1 - Capacitance & Tan Delta Test Unit

 

The OMICRON CP TD1 is a precision diagnostic module designed to assess the insulation condition of high-voltage electrical equipment. Compatible with CPC 100, CPC 80, or TESTRANO systems, it performs capacitance and dissipation factor (tan b4 / power factor) measurements with laboratory-grade accuracy, enabling early detection of insulation aging, moisture ingress, and dielectric losses.

 

Features & Benefits

 

  • Test voltage up to 12 kV AC for comprehensive insulation testing
  • Frequency sweep range of 15400 Hz enhances diagnostic sensitivity
  • Measures capacitance, tan b4 (DF), power factor, impedance, and phase angle
  • Integrated high-voltage source, reference capacitor, and measurement electronics
  • High noise suppression allows reliable on-site testing even in high-interference substations
  • Fully automated testing supported by PTM software for user convenience
  • Ideal for transformers, bushings, cables, and rotating machine insulation diagnostics.

 

Material & Build

 

The CP TD1 unit features rugged and precise electronic components integrated into a compact diagnostic module suited for demanding field conditions. It incorporates a high-voltage source and advanced measurement electronics ensuring accurate and stable readings.

 

Use Cases / Applications

 

Designed to support condition-based maintenance programs, the CP TD1 is highly effective in diagnosing insulation health of transformers, bushings, power cables, and rotating electrical machines, aiding early fault detection and asset reliability improvement.

Omicron CP TD1 - Capacitance & Tan Delta Test Unit

SKU: 1004
Cantidad
  • DATASHEET

  • SPECIFICATIONS

    1. Key Performance & Electrical

     

    • Application Focus: High-voltage reference source and measurement unit designed to work in conjunction with the OMICRON CPC series test systems for precise power/dissipation factor (tanδ) and capacitance diagnostics on high-voltage assets like power transformers, bushings, circuit breakers, cables, and rotating machines.

    • High-Voltage Output:

      • Voltage Range: 0 to 12 kV AC

      • Output Current: Up to 300 mA

      • Output Power: Up to 3.6 kVA at 12 kV

    • Variable Test Frequency Range: 15 Hz to 400 Hz (with a fine resolution of 0.01 Hz) for advanced frequency-domain spectroscopic evaluation of insulation aging.

    • Measured Parameters: Power Factor (cosφ), Dissipation Factor (tanδ), Capacitance (C), Inductance, Impedance, Exciting Current, Active/Reactive/Apparent Power, and Quality Factor (QF).

    • Interference Suppression: Advanced digital filtering architecture built to effectively mitigate high mains frequency interference fields for reliable on-site testing.

     

    2. General & Physical

     

    • System Integration: Directly controlled via the primary test system interface with automated voltage and frequency sweep execution.

    • Safety Features: Integrated emergency stop button, safety key lock, ground connection monitor, and support for external safety warning lights/interlocks.

    • Dimensions (CP TD1 Unit & Transport Case): Approx. 700 × 500 × 420 mm.

    • Weight: Approx. 38.1 kg for the main unit setup; engineered with lightweight modular transport components.

    • Operating Temperature Range: -10 °C to +55 °C at 5% to 95% non-condensing relative humidity.

  • RENTAL DETAILS & LOGISTICS

    Rental Terms

    1 Day minimum

    Extension Terms  Flexible Weekly / Monthly Extensions
    Delivery Nationwide & International
    Support  24x7 on-call + on-site support
    Availability UAE, Bahrain, Saudi Arabia, Spain
  • RENTAL INQUIRIES & CONTACT

    For rental inquiries, contact Skysun Energy via email at support@skysunenergy.com or by phone depending on the country you require.

    • Bahrain: +973 3312 1984

    • Saudi Arabia: +966 509674576

    • UAE: +971 5257 97530

    • Spain: +34 603987120

Found what you need? Get in touch and secure your rental today