BAUR Viola TD - VLF Cable Test and Diagnostics System
The Baur Viola TD is an advanced Very Low Frequency (VLF) test system engineered for thorough testing and diagnostics of medium-voltage (MV) cables and electrical equipment. This device integrates VLF withstand testing with tan delta (dissipation factor) measurement and Monitored Withstand Test (MWT), providing precise evaluation of insulation conditions, aging, and moisture-related defects to help ensure network reliability.
Features & Benefits
- Maximum test voltage of up to approximately 44 kVrms / 60–62 kV peak for robust insulation testing.
- Operates at a frequency of typically 0.1 Hz using VLF truesinus® technology for accurate results.
- Supports multiple voltage modes including VLF sine, rectangular waveforms, and DC testing.
- Highly precise tan delta measurement with accuracy up to 1 × 10⁻⁴ for sensitive insulation diagnostics.
- Incorporates Monitored Withstand Test (MWT) combining withstand voltage and tan delta diagnostics.
- Compatible for MV cables up to 35 kV, suitable for commissioning and maintenance tasks.
- Fully automated test sequences with USB data management enable efficient workflow and data handling.
- Compliant with international standards IEEE 400.2, IEC 60060-3, and IEC 60502 ensuring reliable and accepted test procedures.
Material & Build
The system is built with rugged, precision electronic components designed for field and lab use. Its robust enclosure protects delicate instrumentation to maintain accuracy over time, while its user-friendly interfaces simplify operation even in challenging environments.
Use Cases / Applications
- VLF withstand testing for commissioning new MV cables.
- Insulation diagnostics for aging MV cable inventories.
- Condition-based maintenance programs focused on preventing unexpected cable failures.
- Moisture ingress and partial discharge detection in cable insulation systems.
- Data-driven prioritization of cable replacement or repair strategies.
BAUR Viola TD - VLF Cable Test and Diagnostics System
DATASHEET
SPECIFICATIONS
1. Key Performance & Electrical
-
Application Focus: Very Low Frequency (VLF) AC voltage testing, cable sheath testing, and advanced cable diagnostics (dissipation factor/tan δ and Monitored Withstand Testing) for medium-voltage cables up to 35 kV, electrical equipment, generators, transformers, and switchgear
-
Test Voltage Shapes: VLF truesinus® (load-independent, reproducible sinusoidal voltage), VLF rectangular wave voltage, and direct current (DC) voltage
-
Output Voltage Range:
-
VLF truesinus®: 1 to 44 kV rms (62 kV peak)
-
VLF Square Wave: 1 to 60 kV
-
DC Voltage: ±1 to 60 kV
-
Voltage Resolution & Accuracy: 0.1 kV resolution; ±1% accuracy
-
-
Output Current & Capacitive Load:
-
Measurement Range: 0 to 70 mA (1 µA resolution, ±1% accuracy)
-
Maximum Capacitive Load: 0.85 µF at 0.1 Hz (up to 10 µF at reduced frequencies)
-
-
Dissipation Factor (Tanδ) Measurement (Viola TD):
-
Load Range: 10 nF to 10 µF
-
Measurement Range: 1 X 10-4 to 21,000 X 10-3 (Resolution: 1 X 10-6, Accuracy: 1 X 10 -4)
-
Frequency: 0.1 Hz VLF truesinus®
-
-
Safety Architecture: Integrated automatic discharge unit, reverse voltage protection up to 13 kV, and connection port for an external emergency stop unit.
2. General & Physical
-
System Architecture: Two-part portable modular design separating the high-voltage (HV) unit from the operating unit for easier field transport and setup
-
Input Power Supply: 100 to 260 V, 50/60 Hz (Max power consumption: 1,400 VA)
-
Data Management & Interface: USB 2.0 data interface for test log export and evaluation via Excel-based Diagnostic Reporter software
-
Enclosure & Protection: IP24 rating
-
Dimensions (W x H x D, excluding cable compartment):
-
HV Part: 505 × 503 × 405 mm
-
Operating Unit: 505 × 433 × 405 mm
-
Total Two-Part Setup: 505 × 854 × 405 mm
-
-
Weights:
-
HV Part: Approx. 57 kg
-
Operating Unit: Approx. 19 kg
-
-
Operating Temperature Range: -10 °C to +50 °C
-
RENTAL DETAILS & LOGISTICS
Rental Terms 1 Day minimum
Extension Terms Flexible Weekly / Monthly Extensions Delivery Nationwide & International Support 24x7 on-call + on-site support Availability UAE, Bahrain, Saudi Arabia, Spain RENTAL INQUIRIES & CONTACT
For rental inquiries, contact Skysun Energy via email at support@skysunenergy.com or by phone depending on the country you require.
-
Bahrain: +973 3312 1984
-
Saudi Arabia: +966 509674576
-
UAE: +971 5257 97530
-
Spain: +34 603987120
-